CFM, ACH and equivalent clean air
Air Changes per Hour Calculator
See how much air changes in a room and how much particle filtration contributes. Compare clean outdoor ventilation, filtered HVAC recirculation, and portable purifier CADR against your target.
Calculate clean air by source
Use measured airflow for the same room. Leave a source blank if you cannot quantify it or do not want to count it.
Combined particle clean air
- Clean outdoor ventilation
- 1.00 ACH
- HVAC particle filtration
- 1.00 eACH
- Portable particle filtration
- 3.00 eACH
- Additional clean air to reach target
- 0.0 CFM
Filtration contributes equivalent clean air for particles. Its contribution does not increase outdoor air exchange or remove CO₂.
How the ACH and eACH calculations work
- In imperial units, airflow in CFM × 60 ÷ room volume in ft³ gives air changes per hour. In metric units, divide m³/h by m³.
- Average HVAC contribution equals recirculated airflow × particle filter efficiency × the fraction of time the fan is running.
- For a 2,400 ft³ room, 40 CFM of clean outdoor air, 160 CFM of recirculation at 50% efficiency and 50% runtime, and 120 CFM of purifier CADR give 5 equivalent particle air changes per hour.
- The model treats the room as one mixed zone. Use independent contributions for the same space and time period. Do not count supply and exhaust as two independent sources.
Air quality tools for the decision in front of you
Start with the number or question you already have. Every tool leads to a concrete calculation, comparison, or action plan instead of another generic article.
Air purifier size calculator
Calculate smoke CADR, air changes per hour, and purifier count for a room.
CO₂ decay ventilation calculator
Estimate room ventilation from measured indoor and outdoor CO₂, and compare two test conditions.
Indoor PM2.5 calculator
Estimate steady-state indoor PM2.5 from outdoor air, room volume, infiltration, sources, and purifier CADR.
Trust Signals
Verify airflow, filter performance, and outdoor conditions
Review policy
August 8, 2026. We update supporting pages when calculator logic, live data behavior, or source framing changes.
Primary sources
AQI uses EPA / AirNow breakpoint logic. Cigarette-equivalent framing follows Berkeley Earth’s PM2.5 interpretation.
Live data layer
City pages use EPA AirNow where supported, with cached fallbacks and planning baselines if the API fails or coverage is unavailable.
Air changes per hour questions
What is the difference between ACH and eACH?
Outdoor-air ACH is air exchanged with outside. Equivalent ACH expresses the effect of filtration or other particle removal as a clean airflow. Filtration does not remove carbon dioxide or replace outdoor air.
Can I use the MERV number as an efficiency percentage?
No. Use a particle-removal efficiency for the size of particle being evaluated and the airflow the system actually delivers. A MERV rating alone is not a percent.
Should I count outdoor air during a wildfire?
Only count suitable clean outdoor air as a clean-air contribution. The model does not estimate smoke brought in by ventilation. Use local public-health guidance and the indoor PM2.5 tool to explore smoke infiltration.