Measured CO₂ and room ventilation
CO₂ Decay Ventilation Calculator
Estimate ventilation air changes per hour from two indoor CO₂ measurements and an outdoor baseline. Compare two trials such as windows closed and windows open.
Estimate outdoor air changes from CO₂ readings
Use a period after occupants leave. Keep the same sensor in the same room for both indoor readings and measure the outdoor baseline separately.
Estimated ventilation in first test
The estimate applies to the room and conditions during the test. A moved sensor, continuing CO₂ source, or readings close to the outdoor baseline make the estimate unreliable.
How CO₂ decay estimates ventilation
- Use the natural log of (starting indoor ppm − outdoor ppm) divided by (ending indoor ppm − outdoor ppm), then divide by the time elapsed in hours.
- With a measured outdoor baseline of 420 ppm and indoor CO₂ falling from 1,200 to 700 ppm in 30 minutes, the estimate is about 2.05 air changes per hour.
- Choose a period with no continuing CO₂ source and roughly stable outdoor conditions. Keep the indoor sensor in the same room throughout the test.
- A reading equal to or below the outdoor baseline cannot be used as an endpoint. Measurements too close to the baseline are sensitive to sensor error.
Air quality tools for the decision in front of you
Start with the number or question you already have. Every tool leads to a concrete calculation, comparison, or action plan instead of another generic article.
Air changes per hour calculator
Compare clean outdoor ventilation, HVAC particle filtration, and portable purifier CADR against a target.
Indoor PM2.5 calculator
Estimate steady-state indoor PM2.5 from outdoor air, room volume, infiltration, sources, and purifier CADR.
Air purifier size calculator
Calculate smoke CADR, air changes per hour, and purifier count for a room.
Trust Signals
Verify the sensor and compare like-for-like room conditions
Review policy
August 8, 2026. We update supporting pages when calculator logic, live data behavior, or source framing changes.
Primary sources
AQI uses EPA / AirNow breakpoint logic. Cigarette-equivalent framing follows Berkeley Earth’s PM2.5 interpretation.
Live data layer
City pages use EPA AirNow where supported, with cached fallbacks and planning baselines if the API fails or coverage is unavailable.
CO₂ decay calculator questions
Do I need to add CO₂ to the room?
No. Use existing indoor readings after occupants leave. Keep the monitor in the room during both readings and measure the outdoor baseline separately.
Can a HEPA purifier improve the CO₂ decay result?
A particle filter does not remove CO₂. This estimate reflects dilution and exchange, while a purifier provides an additional particle removal contribution.
Can I use this result for every day?
Conditions change with doors, windows, fans, wind, and temperature. The estimate applies to the room and test conditions, and is not a ventilation compliance result.